Duenne non è un rivenditore autorizzato BECKHOFF
EK1110 – BECKHOFF
Technical data EK1110
Task within EtherCAT system conversion of the E-bus signals to 100BASE-TX Ethernet for extension of the EtherCAT network
Data transfer medium Ethernet/EtherCAT cable (min. Cat.5), shielded
Distance between stations 100 m (100BASE-TX)
Protocol any EtherCAT protocol
Delay approx. 1 µs
Data transfer rates 100 Mbit/s
Configuration not required
Bus interface 1 x RJ45
Power supply from E-bus
Current consumption E-bus typ. 130 mA
Electrical isolation 500 V (supply voltage/Ethernet)
Weight approx. 50 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX
Ex marking II 3 G Ex nA IIC T4 Gc
Design form compact terminal housing with signal LEDs
Material polycarbonate
Dimensions (W x H x D) 44 mm x 100 mm x 68 mm
Installation on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of double slot and key connection
Marking labeling of the BZxxx series
Wiring solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver
Connection cross-section s*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWG s*: AWG 28…14,
st*: AWG 28…14,
f*: AWG 26…16
Stripping length 8…9 mm
Current load power contacts Imax: 10 A
*s: solid wire; st: stranded wire; f: with ferrule
From: 125,00 € IVA esc.
Esaurito