DILEM-10-G – EATON
DILEM-10-G (24VDC) – Power contactor, 3p + 1NO, 4kW / 400V / AC3
010213
SUPPLY PROGRAM
Assortment
Power contactors
Application
Miniature contactor for motors and ohmic loads
Below range
DILEM power contactors
Use category
AC-1: Non-inductive or weakly inductive load, resistance furnaces
AC-3 / AC-3e: squirrel-cage motors: starting, stopping during operation
AC-4: Squirrel-cage motors: starting, electric counter-current brakes, reversing, movements impulse
Note
Can also be used for IE3 efficiency class motors.
Also tested in accordance with AC-3e.
Types of connection
Screw terminals
Description
With auxiliary contacts
Poly
3-pole
Rated operational current
AC-3
380 V 400 V [I e ]
9 A
AC-1
conventional free air thermal current, 3 poles, 50 – 60 Hz
per day
at 40 ° C [I th =I and ]
22 A
Max. Rated power of use for three-phase motors 50 – 60 Hz
AC-3
220 V 230 V [P]
2.2 kW
AC-3
380 V 400 V [P]
4 kW
AC-3
660 V 690 V [P]
4 kW
AC-4
220V 230V [P]
1.5 kW
AC-4
380 V 400 V [P]
3 kW
AC-4
660 V 690 V [P]
3 kW
Contact equipment
NA = norm. open
1 NO contact
Note
Combination diode-resistance integrated in the coil
use with
… DILEM
… DILE
Control voltage
24 V DC
Type of current AC / DC
Direct current control
TECHNICAL DATA
Generality
Compliance with standards
IEC / EN 60947, VDE 0660, CSA, UL,
Mechanical life [Operations]
20 x 10 6
Maximum operating frequency
mechanics
9000 Man / h
Maximum operating frequency
electrical (contactors without thermal relay) [Operations / h]
Page 05/070
Suitability for climates
Humid heat, constant, according to IEC 60068-2-78
Humid heat, cyclic according to IEC 60068-2-30
Room temperature
per day
-25 – +50 ° C
Room temperature
in custody
– 25 – 40 ° C
Room temperature
Storage
Ambient storage temperature min.
-40 ° C
Room temperature
Storage
Ambient temperature storage max.
+80 ° C
Mounting position
optional, except vertical with A1 / A2 terminals at the bottom
hock resistance (IEC / EN 60068-2-27)
Sinusoidal shock 10 ms
Basic unit without auxiliary contact module
Main contacts NO contact
10 g
Shock resistance (IEC / EN 60068-2-27)
Sinusoidal shock 10 ms
Basic unit without auxiliary contact module
Auxiliary contacts NC contact / NO contact
NO contact
8 g
Shock resistance (IEC / EN 60068-2-27)
Sinusoidal shock 10 ms
Basic device with auxiliary contact module
Main contact NO contact
NO contact
10 g
Shock resistance (IEC / EN 60068-2-27)
Sinusoidal shock 10 ms
Basic device with auxiliary contact module
Auxiliary contacts NO contact / NC contact
20/20 g
Degree of protection
IP20
Protection against accidental contact in case of frontal actuation (EN 50274)
Protection against finger and back of hand contact
Altitude
max. 2000 mm
Weight
0.206 kg
Auxiliary and main circuit connection sections
Screw terminals
Stiff
1 x (0.75 – 2.5)
2 x (0.75 – 2.5) mm 2
Auxiliary and main circuit connection sections
Screw terminals
Flexible with ferrule
1 x (0.75 – 1.5)
2 x (0.75 – 1.5) mm 2
Auxiliary and main circuit connection sections
Screw terminals
Single wire or stranded
18 – 14 AWG
Auxiliary and main circuit connection sections
Screw terminals
Stripping length
8 mm
Auxiliary and main circuit connection sections
Screw terminals
Connecting screw
M3.5
Auxiliary and main circuit connection sections
Screw terminals
Pozidriv screwdriver
2 Size
Auxiliary and main circuit connection sections
Screw terminals
Flat-blade screwdriver
0.8 x 5.5
1 x 6 mm
Auxiliary and main circuit connection sections
Screw terminals
Max. Clamping force
1.2 Nm
Main circuit
Rated impulse withstand voltage [U imp ]
6000 V AC
Overvoltage category / pollution degree
III / 3
Rated insulation voltage [U i ]
690 V AC
Rated operational voltage [U e ]
690 V AC
Safe isolation according to EN 61140
between coil and contacts
300 V AC
Safe isolation according to EN 61140
between contacts
300 V AC
Making capacity (cos ϕ according to IEC / EN 60947)
110 A
Opening power
220V 230V
90 A
Opening power
380 V 400 V
90 A
Opening power
500 V
64 A
Opening power
660 V 690 V
42 A
Short circuit protection fuse max
Tipe “2”, 500 V [gG / gL]
10 A
Short circuit protection fuse max
Tipe “1”, 500 V [gG / gL]
20 A
Alternating voltage
AC-1
Rated operational current
conventional free air thermal current, 3 poles, 50 – 60 Hz
per day
at 40 ° C [I th =I and ]
22 A
AC-1
Rated operational current
conventional free air thermal current, 3 poles, 50 – 60 Hz
per day
at 50 ° C [I th =I and ]
20 A
AC-1
Rated operational current
conventional free air thermal current, 3 poles, 50 – 60 Hz
per day
at 55 ° C [I th =I and ]
19 A
AC-1
Rated operational current
conventional free air thermal current, 3 poles, 50 – 60 Hz
in custody [I th ]
16 A
AC-1
Rated operational current
conventional free air thermal current, 3 poles, 50 – 60 Hz
Note
For the maximum permissible ambient temperature.
AC-1
Rated operational current
Conventional thermal current 1 pole
Note
For the maximum permissible ambient temperature.
AC-1
Rated operational current
Conventional thermal current 1 pole
per day [I th ]
50 A
AC-1
Rated operational current
Conventional thermal current 1 pole
in custody [I th ]
40 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
Note
At maximum allowable ambient temperature (open)
Also tested in accordance with AC-3e.
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
220V 230V [I e ]
9 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
240 V [I e ]
9 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
380 V 400 V [I e ]
9 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
415 V [I e ]
9 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
440 V [I e ]
9 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
500 V [I e ]
6.4 A
AC-3
Rated operational current
open, 3 poles, 50 – 60 Hz
660 V 690 V [I e ]
4.8 A
AC-3
Rated absorbed power [P]
220 V 230 V [P]
2.2 kW
AC-3
Rated absorbed power [P]
240 V [P]
2.5 kW
AC-3
Rated absorbed power [P]
380 V 400 V [P]
4 kW
AC-3
Rated absorbed power [P]
415 V [P]
4.3 kW
AC-3
Rated absorbed power [P]
440 V [P]
4.6 kW
AC-3
Rated absorbed power [P]
500 V [P]
4 kW
AC-3
Rated absorbed power [P]
660 V 690 V [P]
4 kW
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
Note
For the maximum permissible ambient temperature.
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
220V 230V [I e ]
6.6 A
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
240 V [I e ]
6.6 A
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
380 V 400 V [I e ]
6.6 A
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
415 V [I e ]
6.6 A
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
440 V [I e ]
6.6 A
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
500 V [I e ]
5 A
AC-4
Rated operational current
open, 3 poles, 50 – 60 Hz
660 V 690 V [I e ]
3.4 A
AC-4
Rated absorbed power [P]
220V 230V [P]
1.5 kW
AC-4
Rated absorbed power [P]
240 V [P]
1.8 kW
AC-4
Rated absorbed power [P]
380 V 400 V [P]
3 kW
AC-4
Rated absorbed power [P]
415 V [P]
3.1 kW
AC-4
Rated absorbed power [P]
440 V [P]
3.3 kW
AC-4
Rated absorbed power [P]
500 V [P]
3 kW
AC-4
Rated absorbed power [P]
660 V 690 V [P]
3 kW
Continuous voltage
Rated operational current open
DC-1
12 V [I e ]
20 A
Rated operational current open
DC-1
24 V [I e ]
20 A
Rated operational current open
DC-1
60 V [I e ]
20 A
Rated operational current open
DC-1
110 V [I e ]
20 A
Rated operational current open
DC-1
220 V [I e ]
20 A
Electromagnetic system
Voltage safety
Direct current control
Excitation voltage
0.8 – 1.1
Absorbed power
Direct current control
Absorbed power Excitation = Retention
2.3 VA / W
Absorbed power
Direct current control
Note
Pure direct voltage or three-phase bridge rectifiers
Duration of insertion
100% on duration
Operating times at 100% U c
NA contacts
Closing time
Closing time min.
26 ms
Operating times at 100% U c
NA contacts
Closing time
Closing time max.
35 ms
Operating times at 100% U c
NA contacts
Opening time
Opening time min.
15 ms
Operating times at 100% U c
NA contacts
Opening time
Opening time max.
25 ms
Operating times at 100% U c
NA contacts
Closing time with front mounted auxiliary contact
70 ms
Operating times at 100% U c
Reversers
Switching time at 110% U c
Switching time min.
40 ms
Operating times at 100% U c
Reversers
Switching time at 110% U c
Switching time max.
50 ms
Operating times at 100% U c
Reversers
Arc time at 690 V AC
12 ms
Ohmic losses (3 or 4 poles)
with I th , 50 ° C
4.4 W
with I and according to AC-3/400 V
0.9 W
Impedance per pole
7.86 mΩ
Auxiliary contacts
Forced guidance of the contact elements according to EN 60947-5-1 Annex L, including auxiliary contact module
Yup
Rated impulse withstand voltage [U imp ]
6000 V AC
Overvoltage category / pollution degree
III / 3
Rated insulation voltage [U i ]
690 V AC
Rated operational voltage [U e ]
600 V AC
Safe isolation according to EN 61140
between the coil and the contacts
300 V AC
Safe isolation according to EN 61140
between the auxiliary contacts
300 V AC
Rated operational current
AC-15
220 V 240 V [I e ]
6 A
Rated operational current
AC-15
380 V 415 V [I e ]
3 A
Rated operational current
AC-15
500 V [I e ]
1.5 A
Rated operational current
DC L / R ≦ 15 ms
Contacts in series:
1 [24 V]
2.5 A
Rated operational current
DC L / R ≦ 15 ms
Contacts in series:
2 [60 V]
2.5 A
Rated operational current
DC L / R ≦ 15 ms
Contacts in series:
3 [100 V]
1.5 A
Rated operational current
DC L / R ≦ 15 ms
Contacts in series:
3 [220 V]
0.5 A
Conventional thermal current [I th ]
10 A
Safety against false maneuvers [Frequency of failure]
<10 -8 ,