Duenne non è un rivenditore autorizzato

DILM1000-XHI11-SI – EATON

DILM1000-XHI11-SI – Auxiliary contact module, 2-pole, I ° = 10 A, 1 NO contact, 1 NC contact, Side mounting, Screw terminals, DILM40 – DILM225A, -SI
EATON 278425
SUPPLY PROGRAM
accessories
Auxiliary contact modules
Description
with forcibly guided contacts
Function
for standard applications
Poly
2-pole
Types of connection
Screw terminals
Rated operational current
Conventional thermal current 1 pole
per day
a 60 °C [I°]
10 A
AC-15
220 V 230 V 240 V [I e ]
4 A
AC-15
380 V 400 V 415 V [I e ]
4 A
AC-15
380 V 400 V 500 V [I e ]
4 A
Contact equipment
NA = norm. open
1 NO contact
NC = norm. Closed
1 NC contact
Mounting type
Side mounting
use with
DILM40 – DILM225A
DILMP63 – DILMP200
DILMF40 – DILMF95
Execution
Side auxiliary contacts
Note
Forcibly guided contacts, according to IEC / EN 60947-5-1 Annex L, inside the auxiliary contact modules Auxiliary
NC contact usable as mirror contact according to IEC / EN 60947-4-1 Annex F (non delayed NC contact)
TECHNICAL DATA
Generality
Compliance with standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan of the appliance
with U e = 230 V, AC-15, 3 A [Operations]
1.3 x 106
Suitability for climates
Humid heat, constant, according to IEC 60068-2-78
Humid heat, cyclic according to IEC 60068-2-30
Room temperature
per day
-25 – +60 °C
Room temperature
in custody
– 25 – 40 °C
Room temperature
Ambient storage temperature
-40 – 80 °C
Degree of protection
IP20
Protection against accidental contacts in case of frontal actuation (EN 50274)
Protection against finger contact and back of hand
Weight
0.041 kg
Connection sections
Screw terminals
Stiff
1 x (0,75-2,5)
2 x (0,75-2,5) mm2
Connection sections
Screw terminals
Flexible with ferrule
1 x (0,75-2,5)
2 x (0,75-2,5) mm2
Connection sections
Screw terminals
Single wire or stranded
18 – 14 AWG
Connection sections
Screw terminals
Pozidriv screwdriver
2 Size
Connection sections
Screw terminals
Flat-blade screwdriver
0.8 x 5.5
1 x 6 mm
Connection sections
Screw terminals
Max. Clamping force
1.2 Nm
Relay contacts
Forced guidance of the contact elements within an auxiliary contact module (in accordance with IEC 60947-5-1 Annex L)
Yup
NC contact (not delayed) suitable as mirror contact (in accordance with IEC / EN 60947-4-1 Appendix F)
DILM40 – DILM225A
Rated impulse withstand voltage [U imp ]
6000 V AC
Overvoltage category / pollution degree
III/3
Rated insulation voltage [U i ]
690 V AC
Rated operational voltage [U e ]
500 V AC
Safe isolation according to EN 61140
between the coil and the contacts
440 V AC
Safe isolation according to EN 61140
between auxiliary contacts
440 V AC
Safe isolation according to EN 61140
between auxiliary contacts and main contacts
440 V AC
Rated operational current
Conventional thermal current 1 pole
a 60 °C [I°]
10 A
Rated operational current
AC-15
220 V 230 V 240 V [I e ]
4 A
Rated operational current
AC-15
380 V 400 V 415 V [I e ]
4 A
Rated operational current
AC-15
500 V [I e ]
1.5 A
Rated operational current
DC
Switch-on and switch-off conditions according to DC-13, constant L / R according to specification.
Rated operational current
DC
DC L/R ≦ 15 ms
Contacts in series:
1 [24 V]
10 A
Rated operational current
DC
DC L/R ≦ 15 ms
Contacts in series:
1 [60V]
6 A
Rated operational current
DC
DC L/R ≦ 15 ms
Contacts in series:
1 [110V]
3 A
Rated operational current
DC
DC L/R ≦ 15 ms
Contacts in series:
1 [220V]
1 A
Rated operational current
DC
DC-13 (6xP)
24 V [I e ]
2 A
Rated operational current
DC
DC-13 (6xP)
60 V [I e ]
1.5 A
Rated operational current
DC
DC-13 (6xP)
110 V [I e ]
0.8 A
Rated operational current
DC
DC-13 (6xP)
220 V [I e ]
0.3 A
Rated operational current
Safety against false maneuvers [Frequency of failure]
<10 -8 ,

Disponibile

I più venduti: