Duenne non è un rivenditore autorizzato

DILM17-32 - EATON

DILM17-32(RDC24) – Contactor, 380 V 400 V 7.5 kW, 3 N/O, 2 NC, RDC 24: 24 – 27 V DC, DC operation, Screw terminals
DELIVERY PROGRAM
Product range
Contactors
Application
Contactors for Motors
Subrange
Complete devices up to 170 A
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Connection technique
Notes
Also suitable for motors with efficiency class IE3.
Also tested according to AC-3e.
Rated operational current
AC-3
380 V 400 V [Ie]
18 A
AC-1
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 40 °C [Ith =Ie]
40 A
AC-1
Conventional free air thermal current, 3 pole, 50 – 60 Hz
enclosed [Ith ]
32 A
AC-1
Conventional free air thermal current, 1 pole
open [Ith ]
88 A
AC-1
Conventional free air thermal current, 1 pole
enclosed [Ith ]
80 A
Max. rating for three-phase motors, 50 – 60 Hz
AC-3
220 V 230 V [P]
5 kW
AC-3
380 V 400 V [P]
7.5 kW
AC-3
660 V 690 V [P]
11 kW
AC-4
220 V 230 V [P]
2.5 kW
AC-4
380 V 400 V [P]
4.5 kW
AC-4
660 V 690 V [P]
6.5 kW
Contacts
N/O = Normally open
3 N/O
N/C = Normally closed
2 NC
Instructions
Contacts to EN 50 012.
integrated suppressor circuit in actuating electronics
with mirror contact.
Contact sequence
210S166
Actuating voltage
RDC 24: 24 – 27 V DC
Voltage AC/DC
DC operation
TECHNICAL DATA
General
Standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
DC operated [Operations]
10 x 106
Operating frequency, mechanical
DC operated [Operations/h]
5000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open
-25 – +60 °C
Ambient temperature
Enclosed
– 25 – 40 °C
Ambient temperature
Storage
– 40 – 80 °C Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/C contact
5 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact
6.9 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/O contact
5.3 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/C contact
3.5 g
Degree of Protection
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Altitude
Max. 2000 m
Weight
DC operated
0.48 kg
Screw connector terminals
Terminal capacity main cable
Solid
1 x (0.75 – 16)
2 x (0.75 – 10) mm2
Screw connector terminals
Terminal capacity main cable
Flexible with ferrule
1 x (0.75 – 16)
2 x (0.75 – 10) mm2
Screw connector terminals
Terminal capacity main cable
Stranded
1 x 16 mm2
Screw connector terminals
Terminal capacity main cable
Solid or stranded
single 18 – 6, double 18 – 8 AWG
Screw connector terminals
Terminal capacity main cable
Stripping length
10 mm
Screw connector terminals
Terminal capacity main cable
Terminal screw
M5
Screw connector terminals
Terminal capacity main cable
Tightening torque
3.2 Nm
Screw connector terminals
Terminal capacity main cable
Tool
Pozidriv screwdriver
2 Size
Screw connector terminals
Terminal capacity main cable
Tool
Standard screwdriver
0.8 x 5.5
1 x 6 mm
Screw connector terminals
Terminal capacity control circuit cables
Solid
1 x (0.75 – 2.5)
2 x (0.75 – 2.5) mm2
Screw connector terminals
Terminal capacity control circuit cables
Flexible with ferrule
1 x (0.75 – 2.5)
2 x (0.75 – 2.5) mm2
Screw connector terminals
Terminal capacity control circuit cables
Solid or stranded
18 – 14 AWG
Screw connector terminals
Terminal capacity control circuit cables
Stripping length
10 mm
Screw connector terminals
Terminal capacity control circuit cables
Terminal screw
M3.5
Screw connector terminals
Terminal capacity control circuit cables
Tightening torque
1.2 Nm
Screw connector terminals
Terminal capacity control circuit cables
Tool
Pozidriv screwdriver
2 Size
Screw connector terminals
Terminal capacity control circuit cables
Tool
Standard screwdriver
0.8 x 5.5
1 x 6 mm
Main conducting paths
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140
between coil and contacts
440 V AC
Safe isolation to EN 61140
between the contacts
440 V AC
Making capacity (p.f. to IEC/EN 60947) [Up to 690 V]
238 A
Breaking capacity
220 V 230 V
170 A
Breaking capacity
380 V 400 V
170 A
Breaking capacity
500 V
170 A
Breaking capacity
660 V 690 V
120 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V [gG/gL 500 V]
35 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
690 V [gG/gL 690 V]
35 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “1” coordination
400 V [gG/gL 500 V]
63 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “1” coordination
690 V [gG/gL 690 V]
50 A
AC
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 40 °C [Ith =Ie]
40 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 50 °C [Ith =Ie]
38 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 55 °C [Ith =Ie]
37 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 60 °C [Ith =Ie]
35 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
enclosed [Ith ]
32 A
AC-1
Rated operational current
Conventional free air thermal current, 1 pole
open [Ith ]
88 A
AC-1
Rated operational current
Conventional free air thermal current, 1 pole
enclosed [Ith ]
80 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
Notes
At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
220 V 230 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
240 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
380 V 400 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
415 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
440V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
500 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
660 V 690 V [Ie]
12 A
AC-3
Motor rating [P]
220 V 230 V [P]
5 kW
AC-3
Motor rating [P]
240V [P]
5.5 kW
AC-3
Motor rating [P]
380 V 400 V [P]
7.5 kW
AC-3
Motor rating [P]
415 V [P]
10 kW
AC-3
Motor rating [P]
440 V [P]
10.5 kW
AC-3
Motor rating [P]
500 V [P]
12 kW
AC-3
Motor rating [P]
660 V 690 V [P]
11 kW
AC-4
Open, 3-pole: 50 – 60 Hz
220 V 230 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
240 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
380 V 400 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
415 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
440 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
500 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
660 V 690 V [Ie ]
8 A
AC-4
Motor rating [P]
220 V 230 V [P]
2.5 kW
AC-4
Motor rating [P]
240 V [P]
3 kW
AC-4
Motor rating [P]
380 V 400 V [P]
4.5 kW
AC-4
Motor rating [P]
415 V [P]
5 kW
AC-4
Motor rating [P]
440 V [P]
5.5 kW
AC-4
Motor rating [P]
500 V [P]
6 kW
AC-4
Motor rating [P]
660 V 690 V [P]
6.5 kW
DC
Rated operational current, open
DC-1
60 V [Ie ]
35 A
Rated operational current, open
DC-1
110 V [Ie ]
35 A
Rated operational current, open
DC-1
220 V [Ie ]
35 A
Current heat loss
3 pole, at Ith (60°)
7.9 W
Current heat loss at Ie to AC-3/400 V
2.1 W
Impedance per pole
2.7 mΩ
Magnet systems
Voltage tolerance
DC operated [Pick-up]
0.7 – 1.2 x Uc
Voltage tolerance
Notes
RDC 24 (Umin 24 V DC/Umax 27 V DC)
Example: US = 0.7 x Umin – 1.2 x Umax / US = 0.7 x 24V – 1.2 x 27V DC
Voltage tolerance
DC operated [Drop-out]
0.15 – 0.6 x Uc
Voltage tolerance
Notes
at least smoothed two-phase bridge rectifier or three-phase rectifier
Power consumption of the coil in a cold state and 1.0 x US
DC operated [Pick-up]
12 W
Power consumption of the coil in a cold state and 1.0 x US
DC operated [Sealing]
0.9 W
Duty factor
100 % DF
Changeover time at 100 % US (recommended value)
Main contacts
DC operated
Closing delay
Closing delay
47 ms
Changeover time at 100 % US (recommended value)
Main contacts
DC operated
Opening delay
Opening delay
30 ms
Changeover time at 100 % US (recommended value)
Arcing time
10 ms
Lifespan, mechanical; Coil 50/60 Hz
Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical data, general” x 106
Electromagnetic compatibility (EMC)
Emitted interference
to EN 60947-1
Interference immunity
to EN 60947-1
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
5 HP
Switching capacity
Maximum motor rating
Three-phase
230 V
240 V
5 HP
Switching capacity
Maximum motor rating
Three-phase
460 V
480 V
10 HP
Switching capacity
Maximum motor rating
Three-phase
575 V
600 V
15 HP
Switching capacity
Maximum motor rating
Single-phase
115 V
120 V
2 HP
Switching capacity
Maximum motor rating
Single-phase
230 V
240 V
3 HP
Switching capacity
General use
40 A
Auxiliary contacts
Pilot Duty
AC operated
A600
Auxiliary contacts
Pilot Duty
DC operated
P300
Auxiliary contacts
General Use
AC
600 V
Auxiliary contacts
General Use
AC
10 A
Auxiliary contacts
General Use
DC
250 V
Auxiliary contacts
General Use
DC
1 A
Short Circuit Current Rating
Basic Rating
SCCR
5 kA
Short Circuit Current Rating
Basic Rating
max. Fuse
125 A
Short Circuit Current Rating
Basic Rating
max. CB
125 A
Short Circuit Current Rating
480 V High Fault
SCCR (fuse)
10/100 kA
Short Circuit Current Rating
480 V High Fault
max. Fuse
125/70 Class J A
Short Circuit Current Rating
480 V High Fault
SCCR (CB)
10/65 kA
Short Circuit Current Rating
480 V High Fault
max. CB
50/32 A
Short Circuit Current Rating
600 V High Fault
SCCR (fuse)
10/100 kA
Short Circuit Current Rating
600 V High Fault
max. Fuse
125/70 Class J A
Short Circuit Current Rating
600 V High Fault
SCCR (CB)
10/22 kA
Short Circuit Current Rating
600 V High Fault
max. CB
50/32 A
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose Ratings
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose Ratings
Incandescent Lamps (Tungsten)
600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose Ratings
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose Ratings
Resistance Air Heating
600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose Ratings
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase
240 A
Special Purpose Ratings
Refrigeration Control (CSA only)
FLA 480V 60Hz 3phase
40 A
Special Purpose Ratings
Refrigeration Control (CSA only)
LRA 600V 60Hz 3phase
180 A
Special Purpose Ratings
Refrigeration Control (CSA only)
FLA 600V 60Hz 3phase
30 A
Special Purpose Ratings
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase
108 A
Special Purpose Ratings
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
FLA 480V 60Hz 3phase
18 A
Special Purpose Ratings
Elevator Control
200V 60Hz 3phase
3 HP
Special Purpose Ratings
Elevator Control
200V 60Hz 3phase
11 A
Special Purpose Ratings
Elevator Control
240V 60Hz 3phase
3 HP
Special Purpose Ratings
Elevator Control
240V 60Hz 3phase
9.6 A
Special Purpose Ratings
Elevator Control
480V 60Hz 3phase
7.5 HP
Special Purpose Ratings
Elevator Control
480V 60Hz 3phase
11 A
Special Purpose Ratings
Elevator Control
600V 60Hz 3phase
10 HP
Special Purpose Ratings
Elevator Control
600V 60Hz 3phase
11 A
DESIGN VERIFICATION AS PER IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
18 A
Heat dissipation per pole, current-dependent [Pvid]
0.7 W
Equipment heat dissipation, current-dependent [Pvid]
2.1 W
Static heat dissipation, non-current-dependent [Pvs]
0.9 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.7 Inscriptions
Meets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard’s requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
TECHNICAL DATA ETIM 8.0
Low-voltage industrial components (EG000017) / Power contactor, AC switching (EC000066)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching (ecl@ss10.0.1-27-37-10-03 [AAB718015])
Rated control supply voltage Us at AC 50HZ
0 – 0 V
Rated control supply voltage Us at AC 60HZ
0 – 0 V
Rated control supply voltage Us at DC
24 – 27 V
Voltage type for actuating
DC
Rated operation current Ie at AC-1, 400 V
40 A
Rated operation current Ie at AC-3, 400 V
18 A
Rated operation power at AC-3, 400 V
7.5 kW
Rated operation current Ie at AC-4, 400 V
10 A
Rated operation power at AC-4, 400 V
4.5 kW
Rated operation power NEMA
7.4 kW
Modular version
No
Number of auxiliary contacts as normally open contact
3
Number of auxiliary contacts as normally closed contact
2
Type of electrical connection of main circuit
Screw connection
Number of normally closed contacts as main contact
0
Number of normally open contacts as main contact
3
APPROVALS
Product Standards
IEC/EN 60947-4-1; UL 60947-4-1; CSA – C22.2 No. 60947-4-1-14; CE marking
UL File No.
E29096
UL Category Control No.
NLDX
CSA File No.
012528
CSA Class No.
2411-03, 3211-04
North America Certification
UL listed, CSA certified
Specially designed for North America
No
DILM17-32(RDC24) – Contactor, 380 V 400 V 7.5 kW, 3 N/O, 2 NC, RDC 24: 24 – 27 V DC, DC operation, Screw terminals
DELIVERY PROGRAM
Product range
Contactors
Application
Contactors for Motors
Subrange
Complete devices up to 170 A
Utilization category
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Connection technique
Notes
Also suitable for motors with efficiency class IE3.
Also tested according to AC-3e.
Rated operational current
AC-3
380 V 400 V [Ie]
18 A
AC-1
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 40 °C [Ith =Ie]
40 A
AC-1
Conventional free air thermal current, 3 pole, 50 – 60 Hz
enclosed [Ith ]
32 A
AC-1
Conventional free air thermal current, 1 pole
open [Ith ]
88 A
AC-1
Conventional free air thermal current, 1 pole
enclosed [Ith ]
80 A
Max. rating for three-phase motors, 50 – 60 Hz
AC-3
220 V 230 V [P]
5 kW
AC-3
380 V 400 V [P]
7.5 kW
AC-3
660 V 690 V [P]
11 kW
AC-4
220 V 230 V [P]
2.5 kW
AC-4
380 V 400 V [P]
4.5 kW
AC-4
660 V 690 V [P]
6.5 kW
Contacts
N/O = Normally open
3 N/O
N/C = Normally closed
2 NC
Instructions
Contacts to EN 50 012.
integrated suppressor circuit in actuating electronics
with mirror contact.
Contact sequence
210S166
Actuating voltage
RDC 24: 24 – 27 V DC
Voltage AC/DC
DC operation
TECHNICAL DATA
General
Standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
DC operated [Operations]
10 x 106
Operating frequency, mechanical
DC operated [Operations/h]
5000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open
-25 – +60 °C
Ambient temperature
Enclosed
– 25 – 40 °C
Ambient temperature
Storage
– 40 – 80 °C Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/C contact
5 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact
6.9 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/O contact
5.3 g
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Auxiliary contacts
N/C contact
3.5 g
Degree of Protection
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Altitude
Max. 2000 m
Weight
DC operated
0.48 kg
Screw connector terminals
Terminal capacity main cable
Solid
1 x (0.75 – 16)
2 x (0.75 – 10) mm2
Screw connector terminals
Terminal capacity main cable
Flexible with ferrule
1 x (0.75 – 16)
2 x (0.75 – 10) mm2
Screw connector terminals
Terminal capacity main cable
Stranded
1 x 16 mm2
Screw connector terminals
Terminal capacity main cable
Solid or stranded
single 18 – 6, double 18 – 8 AWG
Screw connector terminals
Terminal capacity main cable
Stripping length
10 mm
Screw connector terminals
Terminal capacity main cable
Terminal screw
M5
Screw connector terminals
Terminal capacity main cable
Tightening torque
3.2 Nm
Screw connector terminals
Terminal capacity main cable
Tool
Pozidriv screwdriver
2 Size
Screw connector terminals
Terminal capacity main cable
Tool
Standard screwdriver
0.8 x 5.5
1 x 6 mm
Screw connector terminals
Terminal capacity control circuit cables
Solid
1 x (0.75 – 2.5)
2 x (0.75 – 2.5) mm2
Screw connector terminals
Terminal capacity control circuit cables
Flexible with ferrule
1 x (0.75 – 2.5)
2 x (0.75 – 2.5) mm2
Screw connector terminals
Terminal capacity control circuit cables
Solid or stranded
18 – 14 AWG
Screw connector terminals
Terminal capacity control circuit cables
Stripping length
10 mm
Screw connector terminals
Terminal capacity control circuit cables
Terminal screw
M3.5
Screw connector terminals
Terminal capacity control circuit cables
Tightening torque
1.2 Nm
Screw connector terminals
Terminal capacity control circuit cables
Tool
Pozidriv screwdriver
2 Size
Screw connector terminals
Terminal capacity control circuit cables
Tool
Standard screwdriver
0.8 x 5.5
1 x 6 mm
Main conducting paths
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140
between coil and contacts
440 V AC
Safe isolation to EN 61140
between the contacts
440 V AC
Making capacity (p.f. to IEC/EN 60947) [Up to 690 V]
238 A
Breaking capacity
220 V 230 V
170 A
Breaking capacity
380 V 400 V
170 A
Breaking capacity
500 V
170 A
Breaking capacity
660 V 690 V
120 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V [gG/gL 500 V]
35 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
690 V [gG/gL 690 V]
35 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “1” coordination
400 V [gG/gL 500 V]
63 A
Short-circuit rating
Short-circuit protection maximum fuse
Type “1” coordination
690 V [gG/gL 690 V]
50 A
AC
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 40 °C [Ith =Ie]
40 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 50 °C [Ith =Ie]
38 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 55 °C [Ith =Ie]
37 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 60 °C [Ith =Ie]
35 A
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
enclosed [Ith ]
32 A
AC-1
Rated operational current
Conventional free air thermal current, 1 pole
open [Ith ]
88 A
AC-1
Rated operational current
Conventional free air thermal current, 1 pole
enclosed [Ith ]
80 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
Notes
At maximum permissible ambient temperature (open.)
Also tested according to AC-3e.
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
220 V 230 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
240 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
380 V 400 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
415 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
440V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
500 V [Ie]
18 A
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
660 V 690 V [Ie]
12 A
AC-3
Motor rating [P]
220 V 230 V [P]
5 kW
AC-3
Motor rating [P]
240V [P]
5.5 kW
AC-3
Motor rating [P]
380 V 400 V [P]
7.5 kW
AC-3
Motor rating [P]
415 V [P]
10 kW
AC-3
Motor rating [P]
440 V [P]
10.5 kW
AC-3
Motor rating [P]
500 V [P]
12 kW
AC-3
Motor rating [P]
660 V 690 V [P]
11 kW
AC-4
Open, 3-pole: 50 – 60 Hz
220 V 230 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
240 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
380 V 400 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
415 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
440 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
500 V [Ie ]
10 A
AC-4
Open, 3-pole: 50 – 60 Hz
660 V 690 V [Ie ]
8 A
AC-4
Motor rating [P]
220 V 230 V [P]
2.5 kW
AC-4
Motor rating [P]
240 V [P]
3 kW
AC-4
Motor rating [P]
380 V 400 V [P]
4.5 kW
AC-4
Motor rating [P]
415 V [P]
5 kW
AC-4
Motor rating [P]
440 V [P]
5.5 kW
AC-4
Motor rating [P]
500 V [P]
6 kW
AC-4
Motor rating [P]
660 V 690 V [P]
6.5 kW
DC
Rated operational current, open
DC-1
60 V [Ie ]
35 A
Rated operational current, open
DC-1
110 V [Ie ]
35 A
Rated operational current, open
DC-1
220 V [Ie ]
35 A
Current heat loss
3 pole, at Ith (60°)
7.9 W
Current heat loss at Ie to AC-3/400 V
2.1 W
Impedance per pole
2.7 mΩ
Magnet systems
Voltage tolerance
DC operated [Pick-up]
0.7 – 1.2 x Uc
Voltage tolerance
Notes
RDC 24 (Umin 24 V DC/Umax 27 V DC)
Example: US = 0.7 x Umin – 1.2 x Umax / US = 0.7 x 24V – 1.2 x 27V DC
Voltage tolerance
DC operated [Drop-out]
0.15 – 0.6 x Uc
Voltage tolerance
Notes
at least smoothed two-phase bridge rectifier or three-phase rectifier
Power consumption of the coil in a cold state and 1.0 x US
DC operated [Pick-up]
12 W
Power consumption of the coil in a cold state and 1.0 x US
DC operated [Sealing]
0.9 W
Duty factor
100 % DF
Changeover time at 100 % US (recommended value)
Main contacts
DC operated
Closing delay
Closing delay
47 ms
Changeover time at 100 % US (recommended value)
Main contacts
DC operated
Opening delay
Opening delay
30 ms
Changeover time at 100 % US (recommended value)
Arcing time
10 ms
Lifespan, mechanical; Coil 50/60 Hz
Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical data, general” x 106
Electromagnetic compatibility (EMC)
Emitted interference
to EN 60947-1
Interference immunity
to EN 60947-1
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
5 HP
Switching capacity
Maximum motor rating
Three-phase
230 V
240 V
5 HP
Switching capacity
Maximum motor rating
Three-phase
460 V
480 V
10 HP
Switching capacity
Maximum motor rating
Three-phase
575 V
600 V
15 HP
Switching capacity
Maximum motor rating
Single-phase
115 V
120 V
2 HP
Switching capacity
Maximum motor rating
Single-phase
230 V
240 V
3 HP
Switching capacity
General use
40 A
Auxiliary contacts
Pilot Duty
AC operated
A600
Auxiliary contacts
Pilot Duty
DC operated
P300
Auxiliary contacts
General Use
AC
600 V
Auxiliary contacts
General Use
AC
10 A
Auxiliary contacts
General Use
DC
250 V
Auxiliary contacts
General Use
DC
1 A
Short Circuit Current Rating
Basic Rating
SCCR
5 kA
Short Circuit Current Rating
Basic Rating
max. Fuse
125 A
Short Circuit Current Rating
Basic Rating
max. CB
125 A
Short Circuit Current Rating
480 V High Fault
SCCR (fuse)
10/100 kA
Short Circuit Current Rating
480 V High Fault
max. Fuse
125/70 Class J A
Short Circuit Current Rating
480 V High Fault
SCCR (CB)
10/65 kA
Short Circuit Current Rating
480 V High Fault
max. CB
50/32 A
Short Circuit Current Rating
600 V High Fault
SCCR (fuse)
10/100 kA
Short Circuit Current Rating
600 V High Fault
max. Fuse
125/70 Class J A
Short Circuit Current Rating
600 V High Fault
SCCR (CB)
10/22 kA
Short Circuit Current Rating
600 V High Fault
max. CB
50/32 A
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose Ratings
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose Ratings
Incandescent Lamps (Tungsten)
600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose Ratings
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase
40 A
Special Purpose Ratings
Resistance Air Heating
600V 60Hz 3phase, 347V 60Hz 1phase
40 A
Special Purpose Ratings
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase
240 A
Special Purpose Ratings
Refrigeration Control (CSA only)
FLA 480V 60Hz 3phase
40 A
Special Purpose Ratings
Refrigeration Control (CSA only)
LRA 600V 60Hz 3phase
180 A
Special Purpose Ratings
Refrigeration Control (CSA only)
FLA 600V 60Hz 3phase
30 A
Special Purpose Ratings
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase
108 A
Special Purpose Ratings
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
FLA 480V 60Hz 3phase
18 A
Special Purpose Ratings
Elevator Control
200V 60Hz 3phase
3 HP
Special Purpose Ratings
Elevator Control
200V 60Hz 3phase
11 A
Special Purpose Ratings
Elevator Control
240V 60Hz 3phase
3 HP
Special Purpose Ratings
Elevator Control
240V 60Hz 3phase
9.6 A
Special Purpose Ratings
Elevator Control
480V 60Hz 3phase
7.5 HP
Special Purpose Ratings
Elevator Control
480V 60Hz 3phase
11 A
Special Purpose Ratings
Elevator Control
600V 60Hz 3phase
10 HP
Special Purpose Ratings
Elevator Control
600V 60Hz 3phase
11 A
DESIGN VERIFICATION AS PER IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
18 A
Heat dissipation per pole, current-dependent [Pvid]
0.7 W
Equipment heat dissipation, current-dependent [Pvid]
2.1 W
Static heat dissipation, non-current-dependent [Pvs]
0.9 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.7 Inscriptions
Meets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard’s requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the pan

From: 127,00  IVA esc.

Disponibilità: