Static relay for starting – ELR H5-IES-PT / 500AC-3-IOL
2908669 PHOENIX
Connectable three-phase static relay for reversing motors from 3 ~ AC up to 500 V AC, output current: 3 A, with adjustable overload cut-out, emergency stop function up to SIL 3 / PL e and Push-in connection . Connection to IO-Link.
Note for operation If this unit is to be used in conjunction with the CrossPowerSystem power distribution board, the 16 A fuse module holder (article designation: EM-CPS-DA-22.5F / 16A; article number: 1002668) is required to engage the static relay three-phase on the power distribution board.
Product type Three-phase static relays
Operation 100% ED
Number of phases 3
Type of static relay Reverse starter
Maximum power dissipated in nominal conditions 12 W
Switching frequency ≤ 2 Hz (depending on the load)
Maximum dissipated power 4.1 W
Minimum dissipated power 0.88 W
Type of assignment 1
Diet
Supply voltage of the dimensioning control circuit U S 24 V DC
Control supply voltage range 19.2 V DC … 30 V DC
Power supply, control, sizing current I S 65 mA
Protection circuit Overvoltage protection
Prot. Against polarity inversion; Protection diode against reverse polarity in parallel
Power supply: IO-Link
Rated I / O supply voltage 24 V DC (This supply voltage is made available via the IO-Link interface of the IO-Link master.)
Protection circuit Prot. Against polarity inversion
Short circuit protection
Overload protection
Features of insulation
Rated insulation voltage 550 V
Impulsive dimensioning voltage 6 kV
Overvoltage category III
Degree of pollution 2
Insulation characteristics between the control input voltage, the control supply voltage and the auxiliary circuit to the main circuit Safe separation (IEC 60947-1)
Insulation characteristics between the control input voltage, the control supply voltage and the auxiliary circuit Safe separation (IEC 60947-1) with auxiliary circuit ≤ 300 V AC
Safe separation (EN 50178) with auxiliary circuit ≤ 300 V AC
Quick deactivation
Arousal threshold > 33 A
Response time <0.5 s Check Entrance denomination Enable input Rated working voltage U C 24 V DC Activation voltage range 19.2 V DC ... 30 V DC Sizing working current I C 7 mA Switching threshold 9.6 V ("0" signal) 19.2 V (Signal "1") Switching level <5 V DC (for EMERGENCY STOP) Typical switch-off time <30 ms Number of doors 1 Connection COMBICON Connection technique 3 conductors AC output Tens. of exercise of dimensionam. U and 500 V AC Operating voltage range 42 V AC ... 550 V AC Operating current I e 3 A (AC-51) 3 A (AC-53a) Network frequency 50/60 Hz Load current range 180 mA ... 3 A (see derating) Trip curve in accordance with IEC 60947-4-2 Class 10 Cooling time 20 min. (for Auto Reset) Leakage current 0 mA Protection circuit Prot. Against overvoltages; Varistor Control circuit Connection Push-in connection Stripping length 10 mm Rigid conductor section 0.2 mm² ... 2.5 mm² Flexible conductor section 0.2 mm² ... 2.5 mm² Conductor cross section AWG 24 ... 14 Control circuit Connection Push-in connection Stripping length 10 mm Rigid conductor section 0.2 mm² ... 2.5 mm² Flexible conductor section 0.2 mm² ... 2.5 mm² Conductor cross section AWG 24 ... 14 Status reporting Yellow LED Operating voltage indication Green LED Error reporting Red LED Length 22.5 mm Height 127 mm Depth 114 mm Combustion class according to UL 94 V0 (Housing) Environmental conditions Degree of protection IP20 Ambient temperature (operation) -5 ° C ... 55 ° C (take derating into account) Ambient temperature (storage / transport) -40 ° C ... 80 ° C Elevated position ≤ 2000 m UKCA Name UKCA Certificate UKCA compliance UKCA Name UL approval Certificate NLDX.E228652 NRNT.E172140 UKCA Name Safety Integrity Level (SIL, IEC 61508) Marking ≤ 3 Note Safe disarming UKCA Name Performance Level (ISO 13849) Marking And Note Safe disarming UKCA Name category (ISO 13849) Marking ≤ 3 Note Safe disarming UL data SCCR 100 kA (480 V AC (30 A class CC / 30 A class J (High-Fault) fuse)) 5 kA (480 V AC (20 A RK5 fuse (Standard-Fault))) FLA 3 A (480 V AC) Group installation 20 A (class RK5, SCCR 5kA (480 V AC), # 24 - 14 AWG max. Solid and stranded) 30 A (class CC or J, SCCR 100kA (480 V AC), # 24 - 14 AWG max, solid and stranded) Category code NLDX / NRNT Horsepower ratings 0.5 hp (208 V AC) 0.5 hp (230 V AC) 0.5 hp (240 V AC) 1.5 hp (480 V AC) Standards / Provisions Standards / Provisions IEC 60947-1 EN 60947-4-2 IEC 61508 ISO 13849 Mounting type Rail mounting Assembly instructions tileable, for the distance see derating Installation position vertical (horizontal mounting rail, engine start below)